IC60H – earth leakage circuit breaker – 1P + N – B curve – 32 A – 30 mA – 240 V
A9D34832
| Activity | HDCFD |
|---|---|
| Part Number | A9D34832 |
| [ics] Rated Service Breaking Capacity | 7500 A at 240 V AC 50/60 Hz |
| [icw] Rated Short-time Withstand Current | Icw: 250 A during 8/20 µs impulse withstand |
| [Icw] rated short-time withstand current | Icw: 250 A during 8/20 µs impulse withstand |
| [ui] Rated Insulation Voltage | 400 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 4 kV |
| 9 Mm Pitches | 2 |
| Breaking Capacity | 10000 A Icn at 240 V AC 50/60 Hz |
| breaking capacity | 10000 A Icn at 240 V AC 50/60 Hz |
| Breaking Capacity Code | H |
| Circuit Breaker Application | distribution |
| Comb Busbar and Distribution Block Compatibility | NO |
| Contact Position Indicator | yes |
| Curve Code | B |
| Device Location in System | outgoer |
| Earthing System | TN |
| Earth-leakage Protection | integrated |
| Earth-leakage Protection Class | type A |
| Earth-leakage Protection Time Delay | instantaneous |
| Earth-leakage Sensitivity | 30 mA |
| Limitation Class | 3 |
| Locking Options Description | ON/OFF locking facilities |
| Neutral Position | left |
| Number of Protected Poles | 1 |
| Provision for Padlocking | padlockable with padlock Ø 4 mm |
| Residual Current Tripping Technology | voltage dependent |
| suitability for isolation | yes |
| trip unit technology | thermal-magnetic |
| Tropicalisation | 2 |
| Weight | 211.0 g |
| Package1 Length*Width*Height | 2.7 cm x 14.3 cm x 10.3 cm |
| Country of Manufacturing | Thailand |
| [in] Rated Current | 32 A at 50 °C |
| [ue] Rated Operational Voltage | 240 V AC 50/60 Hz |
| ambient air temperature for operation | -15-60 °C |
| ambient air temperature for storage | -40-85 °C |
| colour | white |
| connections – terminals | screw clamp terminal (top) 1-25 mm² rigid without cable end, screw clamp terminal (top) 1-16 mm² flexible, screw clamp terminal (bottom) 1-16 mm² rigid without cable end, screw clamp terminal (bottom) 1-10 mm² flexible |
| control type | toggle |
| depth | 77.5 mm |
| device short name | iC60H RCBO |
| Electrical Durability | 5000 cycles |
| height | 110 mm |
| IP degree of protection | IP20 |
| local signalling | ON/OFF indication |
| mechanical durability | 20000 cycles |
| mounting mode | clip-on |
| mounting support | DIN rail |
| net weight | 205 g |
| network frequency | 50 Hz |
| network type | AC |
| Poles Description | 1P + N |
| Product Name | Acti9 iC60 RCBO |
| product or component type | residual current breaker with overcurrent protection (RCBO) |
| range | Acti9 |
| range of product | Acti9 |
| relative humidity | 95-95 % at 55-55 °C |
| standards | IEC 61009-1, IEC 61009-2-2 |
| Tightening Torque | power circuit: 3.5-3.5 N.m top, power circuit: 2-2 N.m bottom |
| width | 18 mm |
| Wire Stripping Length | power circuit: 13 mm for bottom connection, power circuit: 14 mm for top connection |
| ambient air temperature for operation | -15-60 °C |
| standards | IEC 61009-1, IEC 61009-2-2 |
| local signalling | ON/OFF indication |
| [Ui] rated insulation voltage | 400 V AC 50/60 Hz |
| tightening torque | power circuit: 3.5-3.5 N.m top, power circuit: 2-2 N.m bottom |